Home / Products / Lead-lined drywall & plywood
Clean board.
Stamped, coded, delivered.
Type X drywall laminated in our Gibsonton plant with 2 lb to 8 lb sheet lead. Stacked lead-to-lead so it arrives clean, stamped and color coded so nobody hangs the wrong sheet, and in Florida, delivered and unloaded by our own crew.
- Type X
- 2 lb to 8 lb
- Fed. Spec. QQ-L-201F
- Own trucks in Florida
The board
Lead-lined drywall is fabricated in our Gibsonton plant using high-quality Type X drywall and sheet lead from 2 lb (1/32″, 0.794 mm) to 8 lb (1/8″, 3.175 mm) as backing. We recommend any lead thickness over 1/8″ be backed on plywood instead. Usual and customary lead heights run to 7′, and we can fabricate full-height lengths of 8′ or 10′.
- Drywall in 8′ or 10′ lengths, 5/8″ or 1/2″ thick. 12′ lengths are not produced because of the breakage risk.
- Pricing includes one 2″-wide lead batten strip, the length of the lead height, with every unit.
- Lead meets Fed. Spec. QQ-L-201F, Grade C, 99.9% pure.
- 50 lead screw-cover discs per panel included. They may not be required under NCRP Report 147, but you will have them.



All lead drywall is not the same
If your project includes X-ray rooms for physician offices or hospitals, you should be concerned with the quality of the lead board you buy. If you are not concerned, it will cost you money. 1970 is the year A-fabco began supplying radiation shielding products, and we have tried ever since to tune in to what installers actually run into. Here is what we found, and what we did about it.
Lead-lined plywood
When the physicist orders more than 1/8″ of lead, we laminate the sheet lead to plywood instead of drywall for a rigid, installable panel. Same clean-board handling, same stamping, same batten strips.
Lead thickness and weight
The schedule of commercial lead thicknesses and weights we quote from. Sheet lead is shown first, then plate.
| Thickness (in) | Decimal | mm | lb / sq ft |
|---|---|---|---|
| Sheet lead · tolerance ± 0.005″ | |||
| 1/32″ | .0312 | 0.7937 | 2 |
| 5/128″ | .0391 | 0.9922 | 2-1/2 |
| 1/16″ | .0625 | 1.5875 | 4 |
| 5/64″ | .0781 | 1.9844 | 5 |
| 3/32″ | .0937 | 2.3812 | 6 |
| 1/8″ | .1250 | 3.1750 | 8 |
| 5/32″ | .1562 | 3.9687 | 10 |
| 3/16″ | .1875 | 4.7625 | 12 |
| 1/4″ | .2500 | 6.3500 | 16 |
| 5/16″ | .3125 | 7.9375 | 20 |
| 3/8″ | .3750 | 9.5250 | 24 |
| Lead plate · tolerance ± 0.010″ | |||
| 1/2″ | 0.50 | 12.70 | 30 |
| 3/4″ | 0.75 | 19.05 | 46 |
| 1″ | 1.00 | 25.40 | 60 |
| 1-1/2″ | 1.50 | 38.10 | 90 |
| 2″ | 2.00 | 50.80 | 120 |
| 2-1/4″ | 2.25 | 57.15 | 135 |
| 2-1/2″ | 2.50 | 63.50 | 150 |
| 2-3/4″ | 2.75 | 69.85 | 165 |
| 3″ | 3.00 | 76.20 | 180 |
| 3-1/4″ | 3.25 | 82.55 | 195 |
| 3-1/2″ | 3.50 | 88.90 | 210 |
| Shielding lead is 99.9% pure sheet lead meeting Fed. Spec. QQ-L-201F, Grade C. | |||
Send the room list.
Wall by wall, the physicist’s lead thickness and the heights. We color code the drawings and the board to match.